Energy saving control method research of modular water chillers group operation and pump variable-frequency control based on dynamic air conditioning load requirements analysis ( EI收录)
文献类型:会议论文
英文题名:Energy saving control method research of modular water chillers group operation and pump variable-frequency control based on dynamic air conditioning load requirements analysis
作者:Chunwang, Li[1]; Peizhe, Tian[1]; Fenglan, Wang[2]
第一作者:李春旺
通讯作者:Chunwang, L.
机构:[1] Biochemical Engineering College, Beijing Union University, Beijing, China; [2] Shili Air Conditioning Technology Development Co., Ltd., Beijing, China
第一机构:北京联合大学生物化学工程学院
会议论文集:2010 International Conference on Computer, Mechatronics, Control and Electronic Engineering, CMCE 2010
会议日期:24 August 2010 through 26 August 2010
会议地点:Changchun
语种:英文
外文关键词:Dynamic loads - Energy efficiency - Office buildings - Requirements engineering - Water cooling systems
摘要:According to a ward office building air conditioning system historical operation data, this article analyzed the number of air-conditioning cooling load operation, the time frequency and air conditioning systems circulating water temperature difference trend with air-conditioning load; proposed 4:2:4 group control method to the modular water chillers and air-conditioning water system energy-saving control scheme of variable frequency plus constant temperature difference. Energy-saving control system using Programmable Logic Controller (PLC) as the core controlling device was built, control logic was programmed. The running experiments show a remarkable energy-saving rate of 26.1%, with good energy efficiency and economy effects. ? 2010 IEEE.
参考文献: